UNDERSTANDING ASTM E783: A SIMPLIFIED GUIDE

ASTM E783 – Field Measurement of Air Leakage Through Installed Exterior Windows and Doors

ASTM E783 test - evaluation of air infiltration and exfiltration

ASTM E783 is the industry standard for field measurement of air leakage through installed fenestration systems, including windows, doors, curtain walls, and storefronts. Unlike laboratory tests such as ASTM E283, which evaluate air infiltration under controlled conditions, E783 is performed in situ, within the actual built environment. The procedure is widely used in quality assurance and post-installation compliance verification.

However, the test has critical limitations, particularly when applied to portions of continuous window wall and curtain wall systems. The standard was originally designed for discrete window and door units installed in wall assemblies—not for large, continuous glazing systems that lack defined perimeters. Misapplication of ASTM E783 has led to significant industry-wide misunderstandings and erroneous conclusions regarding building envelope performance. To read more about these limitations, download the full paper: ASTM E783 and All-Glass Facades .

Jump to Section:


Test Procedure

1. Test Chamber Installation

A sealed test chamber is mounted on the interior or exterior face of the fenestration system, isolating the specimen from surrounding air paths. The chamber must be securely sealed to prevent or minimize extraneous air leakage that could skew test results.

ASTM E783 test - evaluation of air infiltration and exfiltration

2. Static Pressure Application

A controlled static pressure differential is applied across the test specimen using a calibrated blower system. The blower exhausts air from or introduces air into the sealed chamber to generate an interior/exterior pressure differential. Typical pressure differentials range from 75 to 300 Pascals (Pa), with project specifications often dictating test pressures.

3. Airflow Measurement

  • The volume of air required to maintain the pressure differential is measured using a calibrated airflow measurement system.
  • The resulting air leakage rate is expressed in cubic feet per minute per square foot of test area (cfm/ft²) or cubic meters per hour per square meter (m³/h·m²). For fenestration systems with operable components, air leakage may also be reported in cubic feet per minute per linear foot of operable crack (cfm/lf) to quantify performance at gasketed seals and vent perimeters.
  • Multiple readings are taken to ensure accuracy and account for environmental variations.

4. Result Interpretation

  • Measured air leakage rates are compared against specified project requirements, building codes, and manufacturer published performance capabilities.
  • A test specimen is deemed compliant if its measured infiltration rate falls within acceptable limits established in project documents or relevant standards (e.g., 2021 IECC Table C402.5.4).

5. Correcting Airflow Measurements for Localized Air Density

One often-overlooked but critical aspect of ASTM E783 testing is the need to correct raw airflow measurements based on the localized air density at the time of testing. Since the volumetric flow rate measured in the field varies with temperature, barometric pressure, and altitude, all results must be converted to Standard Cubic Feet per Minute (SCFM) to ensure accuracy and consistency across different test environments.

Why Localized Air Density Matters

  • Airflow measurement devices report volumetric flow (ACFM – Actual Cubic Feet per Minute), but airflow rates must be normalized to standard conditions (SCFM) to allow for accurate comparisons.
  • Barometric pressure and air temperature fluctuate due to weather, altitude, and indoor HVAC conditions, impacting air density. Without proper correction, test results can overstate or understate actual air leakage rates.
  • Relying on off-site weather data (e.g., from a nearby airport) instead of directly measuring air density at the test location can lead to significant inaccuracies.

Best Practices for Accurate Air Density Measurement

  • Use a calibrated barometer at the test site to record the actual barometric pressure. Do not rely on airport or online weather data, as local variations (e.g., elevation, enclosed spaces) can significantly impact results.
  • Measure the air temperature directly at the airflow measurement device. Indoor conditions and test equipment heat can cause localized deviations from ambient temperature.
  • Apply density correction factors immediately after testing to avoid misinterpreting raw airflow data.
  • Ensure consistency in reporting by specifying whether air leakage results are presented in ACFM or SCFM. Failure to properly convert to SCFM may result in discrepancies when comparing test results to project specifications.

By ensuring proper air density measurement and SCFM conversion, ASTM E783 test results can provide relatively accurate assessments of air infiltration & exfiltration performance. Neglecting this critical step can lead to misleading conclusions, flawed compliance assessments, and disputes over test validity.

^ Back to Top

Limitations and Misapplications of ASTM E783

ASTM E783 is a building envelope performance measurement tool, utilized widely across the construction industry, but its application to large-scale glazed systems—such as continuous window walls and curtain walls—presents fundamental challenges that can lead to misleading results.

1. Lateral Airflow and Uncompartmentalized Systems

Curtain walls and window walls often feature continuous receptor cavities and stack joints that create air pathways between adjacent units. In an uncompartmentalized system such as this, an ASTM E783 test chamber may inadvertently draw air from these interconnected spaces rather than from the exterior environment.

Consequence: The test overestimates or misattributes air infiltration, leading to erroneous conclusions about envelope performance. A system may appear to pass when, in reality, it is experiencing substantial uncontrolled airflow.

2. Misuse of "Tare Tape" to Isolate Specimens

A common workaround involves applying tape to interior gaskets, operable vent perimeters, and frame joints to artificially compartmentalize the test specimen. This "tare tape" method aims to eliminate extraneous leakage but often fails to fully account for air movement through frame joinery, receptor weeps, and mullion reveals.

Consequence: This approach misrepresents the air tightness of the actual installed system, producing test results that do not reflect real-world performance.

Example: If a curtain wall system has hidden air pathways in its frame receptors, sealing a small portion with tape does not prevent leakage elsewhere in the system. The test may register an artificially low air infiltration rate, leading stakeholders to incorrectly conclude that the façade is airtight.

3. ASTM E783 Does Not Assess Whole-Building Air Tightness

Some project teams incorrectly rely on ASTM E783 results to predict overall building air infiltration rates and derive energy usage estimates.

Consequence: ASTM E783 does not provide a whole-building air leakage measurement and should not be used as the sole method for evaluating overall envelope performance. Building owners relying solely on ASTM E783 may face unexpected energy losses and uncontrolled airflow issues despite having "passing" test reports.

Example: If a curtain wall system has hidden air pathways in its frame receptors, sealing a small portion with tape does not prevent leakage elsewhere in the system. The test may register an artificially low air infiltration rate, leading stakeholders to incorrectly conclude that the façade is airtight.

Industry Example: Many high-rise buildings with multiple passing ASTM E783 test reports have later experienced:

  • Extreme stack effect (uncontrollable airflow between floors)
  • Drafty units and thermal discomfort for occupants
  • Unexpected energy consumption due to excessive infiltration/exfiltration
  • Noise issues, sometimes described as "the woodwind section of a forest gnome orchestra"

This underscores why ASTM E783 should be used only as a tool for evaluating localized fenestration performance—not as a predictor of whole-building air tightness.

^ Back to Top

Important Considerations

  • ASTM E783 is a valuable tool for evaluating installed fenestration performance in the field, but it has significant limitations.
  • The procedure was designed for discrete windows and doors—not for continuous glazing systems like window walls and curtain walls.
  • Project teams should avoid using ASTM E783 as the sole means of evaluating whole-building airtightness.
  • Workarounds such as "tare tape" may artificially improve test results without accurately reflecting real-world air leakage rates.
  • If ASTM E783 must be performed on large-scale glazing systems, rigorous pre-test compartmentalization is essential to ensure accurate results.

^ Back to Top

Further Reading: Hightower Labs' Industry Analysis

For a deeper examination of ASTM E783's limitations and misapplications, Hightower Labs has published a technical document detailing industry-wide challenges with this test method. This report outlines how improper test setups and flawed interpretations can lead to critical performance misjudgments.

Click here to download the full paper: ASTM E783 and All-Glass Facades .

^ Back to Top
🔹 Frequently Asked Questions
ASTM E783 is the industry standard for field measurement of air leakage through installed exterior windows and doors. It provides a procedure to determine the air leakage rates of installed exterior windows and doors under specified static air pressure differences.
The test involves sealing a chamber to the interior or exterior face of the fenestration system, applying a controlled static pressure differential using a calibrated blower system, and measuring the air flow required to maintain this pressure. The air leakage rate is then calculated based on these measurements.
ASTM E783 was originally designed for discrete window and door units installed in wall assemblies. Its application to large, continuous glazing systems like curtain walls can lead to misunderstandings and erroneous conclusions regarding building envelope performance. Additionally, the test may induce air leakage that does not occur under natural environmental exposure.
Airflow measurements can vary with temperature, barometric pressure, and altitude. Correcting these measurements to standard conditions ensures accuracy and consistency across different test environments. Without proper correction, test results can overstate or understate actual air leakage rates.
While both standards assess air leakage, ASTM E283 is intended for laboratory testing of fenestration products under controlled conditions, whereas ASTM E783 provides a field procedure for determining air leakage rates of installed exterior windows and doors.

NOTEWORTHY FROM HTL

Independent studies, industry papers, slideshows, video presentations, and other content benefiting those in the industry with the patience to read five pages, and diagrams for the developers.

  • Meet the New UI Design
    ASTM E783 AND ALL-GLASS FACADES

    Industry-wide, invalid and improperly executed ASTM E783 test data are not providing a reliably accurate accounting of the building's air-tightness on window wall and curtain wall systems comprising the majority of envelopes built this century and, consequently, building stakeholders are blind to their property's performance.

  • ssg system scale
    SSG ITEMS OF CONCERN

    In this Notes From The Field article, HTL checks in on the U.S. construction industry's widespread use and mis-use of structural glazing systems.

  • Lean
    BEAM03 PROCEDURE INTRODUCTION

    The BEAM03 procedure introduces a novel approach to evaluating building envelope water resistivity, addressing critical gaps in traditional QAQC practices. BEAM03 delivers reliable, repeatable data for assessing large-scale envelope performance, including complex geometries and system transitions.